XB6-PD2002ST

PROFIBUS-DP Coupler kit (with power supply, end cover )

Occupies small space, fast speed, quick wiring, pluggable terminal blocks

Simple configuration, compatible with the mainstream PROFIBUS masters such as Siemens

High-speed X-bus bus, full load of 32 slave stations, maximum scan cycle 1ms.

Add

Interface Parameters

ProtocolPROFIBUS-DP
Max. Number of IO Modules32
Data Transfer MediumPROFIBUS-DP dedicated cable (shielded twisted pair RS-485 communication cable).
Data Transfer Rates9.6 Kbps ~ 12 Mbps
Distance Between Stations9.6 Kbps ~ 187.5 Kbps : ≤1000 m
500 Kbps: ≤400 m
1500 Kbps: ≤200 m
3000 Kbps ~ 12000 Kbps: ≤100 m
Electrical Isolation

Technical Parameters

Power Supply18~36 VDC
Current ConsumptionsequentMaximum 1600mA (subsequent IO)
WeightAbout 300 grams.
Module Size106*61*47mm
Protect. ClassIP20
Operating Temperature-10~60℃
Storage Temperature-20~75℃
Relative Humidity95%, no condensation
Power InterfacePush-in 3pin