PN7-0016B

PROFINET, Integrated I/O, 16DO, PNP, 0.5A

IP67 protection level, suitable for harsh industrial environments

Based on high-performance communication chips, faster speed

Can switch between input and output functions by configuring DIO channel parameters

The configuration is simple, supporting mainstream PROFINET masters such as Siemens

Add

Interface Parameters

ProtocolPROFINET
Data Transfer MediumCAT5e: UTP or STP(STP recommended)
Distance Between Stations≤100m
Electrical Isolation500V
Bus Connection2×M12,4Pin,D-code,blue

Technical Parameters

Power Supply18~36 VDC
Weight480g
Module Size225×62×35.1mm
Protect. ClassIP67
Operating Temperature-25~+70℃
Storage Temperature-20~75℃
Relative Humidity95 %, no condensation
Power interface2×M12,5Pin,L-code,red
U<sub>S</sub>total currentMax:16A
U<sub>S</sub>power consumption≤40mA
U<sub>L</sub>total currentMax:16A
U<sub>L</sub>power consumption25mA + Sensor Supply Current + Load Output Current
Electrical isolation between GND<sub>S</sub> and GND<sub>L</sub>YES

Digital Output

Nominal Voltage24VDC(±25%)
Number of Outputs16
Transistor PolarityPNP
Load Typeohmic, inductive load
Max. Output CurrentMax: 500mA
Port ProtectionOvercurrent
Electrical Isolation500V
IndicatorGreen LED
Output Interface8×M12,5Pin,A-code
Output total currentMax:8 A(from UL)
Isolation MethodOptocoupler isolation