IP67 protection level, suitable for harsh industrial environments
Supports digital quantity input delay 1.5ms, filters out microsecond invalid signals
Using standard cable wiring is simple and the layout is quick
The configuration is simple, supporting mainstream CC-Link masters such as Mitsubishi
Protocol | CC-Link |
Data Transfer Medium | CC-Link dedicated cable (three-core shielded cable) |
Data Transfer Rates | Five speed rates can be set: 10 Mbps / 5 Mbps / 2.5 Mbps / 625 kbps / 156 kbps |
Distance Between Stations | ≤100 m / ≤160 m / ≤400 m / ≤900 m / ≤1200 m |
Electrical Isolation | 500V |
Bus Connection | IN:M12,4Pin ,A-code,PIN-end,blue OUT:M12,5Pin,A-code,HOLE-end,blue |
Power Supply | 24 VDC(18V~30V) |
Weight | 480g |
Module Size | 225×62×35.1mm |
Protect. Class | IP67 |
Operating Temperature | -25~+70℃ |
Storage Temperature | -40~+85℃ |
Relative Humidity | 95%,no condensation |
Power interface | 2×M12,5Pin,L-code,red |
U<sub>S</sub>total current | Max:16A |
U<sub>S</sub>power consumption | ≤40mA |
U<sub>L</sub>total current | Max:16A |
U<sub>L</sub>power consumption | 25mA + Sensor supply current + load output current |
Electrical isolation between GND<sub>S</sub> and GND<sub>L</sub> | Yes |
Nominal Voltage | 24 VDC(18V~30V) |
Number of Outputs | 16 |
Transistor Polarity | NPN |
Load Type | Resistive load, inductive load |
Max. Output Current | Max:500 mA(from UL) |
Port Protection | Overcurrent protection, short circuit protection |
Electrical Isolation | 500 VAC |
Indicator | green LED |
Output Interface | 8×M12,5Pin,A-code |
Output total current | Max:8 A(from U>sub>L) |
Isolation Method | Optocoupler isolation |