Stronger anti-interference performance, applicable to more scenarios
Terminals distinguish between positive and negative power supply, preventing power leakage and reverse connection
High-speed X-bus backplane bus, output voltage type, adjustable range
Small footprint, fast speed, quick wiring, pluggable terminal blocks
Protocol | X-bus |
Data Transfer Medium | X-bus Backplane Bus |
Bus Interface | Reed Contact |
Data Transfer Rates | 6Mb/s |
Electrical Isolation | YES |
Power Supply | 5VDC(4.5V~5.5V) |
Current Consumption | ≤200mA |
Weight | 110g |
Module Size | 106.4*25.7*72.3mm |
Protect. Class | IP20 |
Operating Temperature | -20℃~+60℃ |
Storage Temperature | -40℃~+80℃ |
Relative Humidity | 95 %, no condensation |
Module Abnormality Self-Recovery | Support |
diagnosis | Support |
Alarm | Support |
Firmware Upgrade | Support |
Analog Outputs | 8 |
Signal Voltage/Current | -10V~+10V、0V~10V、-5V~+5V、0V~5V、1V~5V(Adjustable Range, default is -10V~+10V) |
Resolution | 16bits |
Accurate | At 25℃, ±0.1%, full temperature range ±0.3% |
Electrical Isolation | 500VAC |
Indicator | Green LED |
Signal Type | Voltage type |
Load Impedance | ≥2kΩ |
Channel Response Time | 400us / ch, 400us / 8ch |
Power consumption | 100mA |