Input compatible with NPN/PNP type input, convenient for flexible use
Input supports type1, type3, the input voltage can go up to 11V, adaptable to more types of sensors
Output field measurement supports surge protection, saving the cost of external surge protectors
Terminals distinguish between positive and negative poles of power supply to prevent misconnection or reverse connection
Protocol | X-bus |
Data Transfer Medium | X-bus Backplane Bus |
Bus Interface | Reed Contact |
Data Transfer Rates | 6Mb/s |
Electrical Isolation | YES |
Power Supply | 5VDC(4.5V~5.5V) |
Current Consumption | 100mA |
Weight | 110g |
Module Size | 106.4*25.7*72.3mm |
Protect. Class | IP20 |
Operating Temperature | -20℃~+60℃ |
Storage Temperature | -40℃~+80℃ |
Relative Humidity | 95 %, no condensation |
Module Abnormality Self-Recovery | Support |
diagnosis | Support |
Alarm | Support |
Firmware Upgrade | Support |
Nominal Voltage | 24VDC(20.4V~28.8V) |
Number of Inputs | 16 |
Transistor Polarity | NPN&PNP |
Input Current | 5mA(24VDC) |
Electrical Isolation | 500VAC |
Indicator | Green LED |
"0" Signal Voltage | -3V~+5V/below 0.9mA(PNP) 11V~30V/above 2.1mA(NPN) |
“1” Signal Voltage | 11V~30V/above 2.1mA(PNP) -3V~+5V/below 0.9mA(NPN) |
Input Filter | Default is 3ms, adjustable range is 0~20 ms |
Isolation Method | Optocoupler Isolation |
Reaction Time | <50us |
Input Impedance | 5.4KΩ |
Power consumption | 0.5W |
Nominal Voltage | 24VDC(20.4V~28.8V) |
Number of Outputs | 16 |
Transistor Polarity | PNP |
Load Type | Resistive load, Inductive load, Lamp load |
Max. Output Current | Max:0.5A |
Port Protection | Reverse Protection (Automatic Recovery Mechanism), On-site Surge Protection |
Electrical Isolation | 500VAC |
Indicator | Green LED |
Output Voltage Drop | <1V |
Leakage Current | <10uA |
Reaction Time | <150us |
Isolation Method | Optocoupler Isolation |
Power consumption | 0.5W |